BIOGAS FLARE ELEVATED FLAME – MOD. EL

 

DESCRIPTION

 

The flare consist of a burner installed at elevated position, equipped with a high-energy ignition Pilot and a flame detection system via Thermocouple. The combustion air is natural conveyed from the bottom part of flame shield and the combustion temperature will be max. di 800 °C .
The height of this flare are calculated according to the heat radiation released from burning to the ground and that will ensure an adeguate level of protection to peolple and equipments that are within range of the flare.
This type of Flare develops a luminous flame which extends beyond the top part, so the combustion temperature and emissions monitoring are difficult to control.
The ignition system is automatic type, operated by the electrical panel installed of the flare’s bottom side and initially involves the pilot’s ignition and subsequently the opening of the main Biogas valve.
The gas train and all accessories such as valves, flame arrestor, pressure gauge and other, are installed at ground level.

 


SITE UTILITIES

 

Power supply

Volt

400

Auxiliary circuits Power

Volt

230-24

Frequency

Hz

50

Electrical Insulation (Local Panel)

Gr.

IP54

Electrical Protection (Field equipments)

Gr.

IP65

Instrument Air Type

/

Dry, without oil

Instrument Air Dew point

°C

-25

Instrument Air ( Wet, without Oil)

barg

6

 


DESIGN CODES

73/23/CE et 93/68/CE
EN 60439-1
98/37/CE
EN 746-2
94/9 CE ATEX


SUPPLIER DATA

 

Model

 

EL

Type

 

Elevated Flame

Total Height (from ground)

ml.

4 > 12

Type of support

 

Selfstanding

Gas Pipe Material

 

Aisi 304

Wind Shield

 

Aisi304/309

Burner Material

 

Aisi 316/310

Air Damper Material

 

N.A.

Inlet Flange

 

ANSI B16.5 - 150#

Flame Detector

 

Thermocouple Typ. K

Internal Insulation

 

N.A.

External Insulation (Only in the Top parts lg. 1 ml.)

 

N.A.